Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 4, 2019, 10:34 AM
  • 10_1_1_04062019_035230.mp4

Date
06/04/2019
W/O
766606
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00698
PipeID
P13908
Time
3:34 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6070
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_766606_TV18177_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0089
Downstream MH
18 0088
Dir. of Survey
Downstream
Length Surveyed
356.9 ft.
Total Length
356.9 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
213
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
217
Pipe schematic from manhole 18 0089 to 18 0088
MH: 18 0089MH: 18 0088downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00890 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start163.6 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"206 ft. IS - Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES242.2 ft. IS - Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES258.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"354.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish356.9 ft. MGO - General Observation - CONNECTION IN MH 3 OCLOCK356.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0088

Observation photos (3)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES

    206 ft. - Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES

    242.2 ft. - Infiltration Stain, from 01 to 04 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
354.6SAV
356.9MGOCONNECTION IN MH 3 OCLOCK
258.9TFC
163.6TFC
356.9AMH18 0088
242.2IS
206IS
2SAV
0AMH18 0089
0MWM
0MWL

Properties (6)

additional_info
SC377914
custom_field_two
3
customer
LACSD
datetime
2019-06-04T03:34:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false