Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2019, 06:20 AM
  • 16_1_2_10062019_233511.mp4

Date
06/10/2019
W/O
766606
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00698
PipeID
P13922
Time
11:20 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6563
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
WO_766606_TV18177_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0102
Downstream MH
18 0101
Dir. of Survey
Downstream
Length Surveyed
224.4 ft.
Total Length
224.4 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
151
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
151
Pipe schematic from manhole 18 0102 to 18 0101
MH: 18 0102MH: 18 0101downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION IN MH AT 9 AND 3 OCLOCK0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01021.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES42.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES51.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start56.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"59.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"97 ft. B - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES97.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES107.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"109.1 ft. FS - Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES110.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"158.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"162.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"207.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"210.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"221.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish221.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish224.4 ft. AMH - Downstream Manhole, Survey Ends - 18 0101224.4 ft. MGO - General Observation - CONNECTION IN MH AT 9 AND 3 OCLOCK

Observation photos (6)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    1.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    33.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    42.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    51.9 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    97.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

    109.1 ft. - Fracture Spiral, from 09 to 10 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
33.7CL
207.2TFC
162.1TFC
59.4TFC
97.2FM
1.9SAP
0MWM
97B
0MGOCONNECTION IN MH AT 9 AND 3 OCLOCK
210.5TFC
221.8CM
0MWL
221.8SAP
110.4TFC
42.7CL
224.4AMH18 0101
109.1FS
0AMH18 0102
224.4MGOCONNECTION IN MH AT 9 AND 3 OCLOCK
107.4TFC
51.9CM
56.4TFC
158.8TFC

Properties (6)

additional_info
SC377686
custom_field_two
2
customer
LACSD
datetime
2019-06-10T23:20:12-07:00
documentation
PROPIPE
is_lateral_inspection
false