Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2019, 08:04 AM
  • 12_1_1_11062019_012037.mp4

Date
06/11/2019
W/O
766606
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00698
PipeID
P13911
Time
1:04 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6563
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_766606_TV18177_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0092
Downstream MH
18 0091
Dir. of Survey
Downstream
Length Surveyed
329.2 ft.
Total Length
329.2 ft.
Structural Index
3
Structural Quick
3O21
Structural Rating
245
O&M Index
2
O&M Quick
412L
O&M Rating
136
Overall Index
3
Overall Quick
Overall Rating
381
Pipe schematic from manhole 18 0092 to 18 0091
MH: 18 0092MH: 18 0091downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00924.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start91.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"98.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"119 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES176.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES208.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES226.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"232.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"256.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start302.1 ft. IW - Infiltration Weeper, at 02 o'clock, within 8 inches of joint: YES317.3 ft. IR - Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES327.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish327.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish327.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329.2 ft. AMH - Downstream Manhole, Survey Ends - 18 0091

Observation photos (8)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    4.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    119 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    176.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    208.4 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    256.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Weeper, at 02 o'clock, within 8 inches of joint: YES

    302.1 ft. - Infiltration Weeper, at 02 o'clock, within 8 inches of joint: YES

  • Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES

    317.3 ft. - Infiltration Runner, at 12 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
226.7TFC
302.1IW
327.1FL
176.6FL
327.1DAGS
4.5SAP
327.1SAP
232.6TFC
0MWM
317.3IR
0MWL
256.5FL
0AMH18 0092
329.2AMH18 0091
91.9TFC
208.4FL
119CL
4.5DAGS
98.4TFC

Properties (6)

additional_info
SC377686
custom_field_two
3
customer
LACSD
datetime
2019-06-11T01:04:48-07:00
documentation
PROPIPE
is_lateral_inspection