Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2019, 06:36 AM
  • 15_1_2_10062019_234522.mp4

Date
06/10/2019
W/O
766606
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00698
PipeID
P13921
Time
11:36 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6563
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
22
Purpose
Routine Assessment
Project
WO_766606_TV18177_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0101
Downstream MH
18 0100
Dir. of Survey
Downstream
Length Surveyed
128.5 ft.
Total Length
128.5 ft.
Structural Index
3
Structural Quick
3D21
Structural Rating
80
O&M Index
2
O&M Quick
2D00
O&M Rating
50
Overall Index
3
Overall Quick
Overall Rating
130
Pipe schematic from manhole 18 0101 to 18 0100
MH: 18 0101MH: 18 0100downstream0 ft. MGO - General Observation - CONNECTION IN MH AT 9 AND 3 OCLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 01012.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start11.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES31.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"34.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"83 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"96.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES126.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish126.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish128.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0100

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    11.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    96.5 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
126.6SAP
85.9TFC
31.4TFC
0MGOCONNECTION IN MH AT 9 AND 3 OCLOCK
126.6DAGS
96.5FL
0MWL
128.5AMH18 0100
11.8CL
0MWM
2.3SAP
83TFC
2.3DAGS
0AMH18 0101
34.5TFC

Properties (6)

additional_info
SC377686
custom_field_two
3
customer
LACSD
datetime
2019-06-10T23:36:24-07:00
documentation
PROPIPE
is_lateral_inspection
false