Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 11, 2019, 09:21 AM
  • 1_1_1_11062019_022830.mp4

Date
06/11/2019
W/O
766606
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00698
PipeID
P13892
Time
2:21 AM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6563
Sewer Name
18 SANTA FE STREET TRUNK
City
WHITTIER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_766606_TV18177_MAY2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0076
Downstream MH
18 0075A
Dir. of Survey
Downstream
Length Surveyed
137.7 ft.
Total Length
137.7 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
78
O&M Index
2
O&M Quick
412I
O&M Rating
102
Overall Index
2
Overall Quick
Overall Rating
180
Pipe schematic from manhole 18 0076 to 18 0075A
MH: 18 0076MH: 18 0075Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00760 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area3.6 ft. MGO - General Observation - MAG COAT THROUGHOUT PIPE3.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start52.6 ft. IR - Infiltration Runner, at 08 o'clock, within 8 inches of joint: YES135.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish135.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish135.8 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish137.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0075A137.7 ft. MGO - General Observation - CONNECTION IN MH 9 OCLOCK

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    19 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Infiltration Runner, at 08 o'clock, within 8 inches of joint: YES

    52.6 ft. - Infiltration Runner, at 08 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
3.6MGOMAG COAT THROUGHOUT PIPE
3.6DAGS
3.6SAV
135.8SAV
135.8DAGS
137.7AMH18 0075A
0AMH18 0076
52.6IR
0MWL
19DAE
135.8DAE
137.7MGOCONNECTION IN MH 9 OCLOCK
0MWM

Properties (6)

additional_info
SC377686
custom_field_two
3
customer
LACSD
datetime
2019-06-11T02:21:10-07:00
documentation
PROPIPE
is_lateral_inspection
false