Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 28, 2019, 09:46 AM
  • 1_1_1_28052019_025742.mp4

Date
05/28/2019
W/O
766507
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00188
PipeID
P11004
Time
2:46 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6543
Sewer Name
H JOINT OUTFALL H - UNIT 8E
City
BALDWIN PARK
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
19
Purpose
Routine Assessment
Project
WO_766507_TV15172_MAY2019
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
H 0580
Downstream MH
H 0579
Dir. of Survey
Downstream
Length Surveyed
276.4 ft.
Total Length
276.4 ft.
Structural Index
3
Structural Quick
513J
Structural Rating
272
O&M Index
2
O&M Quick
412J
O&M Rating
112
Overall Index
2
Overall Quick
Overall Rating
384
Pipe schematic from manhole H 0580 to H 0579
MH: H 0580MH: H 0579downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 05800 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start9.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start10.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"19.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"54.8 ft. HVV - Hole Void Visible, from 12 to 01 o'clock, within 8 inches of joint: YES171.6 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"212.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"273.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish273.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish273.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish276.4 ft. AMH - Downstream Manhole, Survey Ends - H 0579276.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK276.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    9.4 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Hole Void Visible, from 12 to 01 o'clock, within 8 inches of joint: YES

    54.8 ft. - Hole Void Visible, from 12 to 01 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    276.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
171.6TBA
276.4AMHH 0579
2DAGS
54.8HVV
212.4TFC
9.4SAP
273.7DAGS
19.1TFC
10.7TFC
0MWM
273.7SSS
2SSS
220.4TFC
276.4MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMHH 0580
0MWL
273.7SAP
276.4MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC378158
custom_field_two
3
customer
LACSD
datetime
2019-05-28T02:46:56-07:00
documentation
PRO PIPE
is_lateral_inspection
false