Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 19, 2019, 08:42 AM
  • 9_1_1_19042019_014742.mp4

Date
04/19/2019
W/O
761615
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00689
PipeID
P13862
Time
1:42 AM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6521
Sewer Name
18 MILLS AVENUE TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_761615_TV18176_APR2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0046
Downstream MH
18 0047
Dir. of Survey
Upstream
Length Surveyed
59.3 ft.
Total Length
59.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 18 0046 to 18 0047
MH: 18 0046MH: 18 0047upstream0 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O' CLOCK AT MH0 ft. AMH - Upstream Manhole, Survey Ends - 18 00472.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish54.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start59.3 ft. MGO - General Observation - CAPPED CONNECTION AT 9 O' CLOCK AT MH59.3 ft. MWL - Water Level, 15 %of cross sectional area59.3 ft. MWM - Water Mark, 35 %of cross sectional area59.3 ft. AMH - Downstream Manhole, Survey Begins - 18 0046

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MGOCAPPED CONNECTION AT 9 O' CLOCK AT MH
59.3MGOCAPPED CONNECTION AT 3 O' CLOCK AT MH
4.4SAP
59.3AMH18 0047
0MWL
56.7SAP
0MWM
0AMH18 0046

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-04-19T01:42:40-07:00
documentation
PROPIPE
is_lateral_inspection
false