Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 19, 2019, 05:19 AM
  • 12_1_1_18042019_224344.mp4

Date
04/18/2019
W/O
761615
Weather
Dry
Operator/Surveyor
E.RUIZ
Sewer ID
Z00689
PipeID
P13874
Time
10:19 PM
Certificate
U-715-07000753
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K6521
Sewer Name
18 MILLS AVENUE TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_761615_TV18176_APR2019
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0060
Downstream MH
18 0059
Dir. of Survey
Downstream
Length Surveyed
402.5 ft.
Total Length
402.5 ft.
Structural Index
3
Structural Quick
4635
Structural Rating
43
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
43
Pipe schematic from manhole 18 0060 to 18 0059
MH: 18 0060MH: 18 0059downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00606.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"36.9 ft. CM - Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES37.5 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES38.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6"59.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"119.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES123.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"134.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES144.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"153 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES154.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"165 ft. FM - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES166.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"198.7 ft. CS - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES206 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"232.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES255.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"256.9 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES264.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"290.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES291.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 6"336.2 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES346.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"380 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"387.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES399.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish402.5 ft. AMH - Downstream Manhole, Survey Ends - 18 0059402.5 ft. MGO - General Observation - CAPPED CONNECTION AT 9 O' CLOCK AT MH402.5 ft. MGO - General Observation - SERVICE CONNECTION AT 3 O' CLOCK AT MH

Observation photos (12)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    37.5 ft. - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    119.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    134.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    153 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    165 ft. - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

    198.7 ft. - Crack Spiral, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    232.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    256.9 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    290.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    336.2 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    387.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

Observations (33)

DistanceCodeObservation
144.9TFA
290.8FM
6.2SAP
37.5FL
166.4TFA
399.4SAP
38.3TF
36.9CM
134.2CM
206TFA
154.2TFA
59.6TFA
198.7CS
346.7TFA
291.8TFA
0MWM
402.5AMH18 0059
153CL
0MWL
402.5MGOCAPPED CONNECTION AT 9 O' CLOCK AT MH
256.9CM
402.5MGOSERVICE CONNECTION AT 3 O' CLOCK AT MH
264.5TFA
165FM
119.2FM
387.6FM
380TFA
35.1TFA
255.2TFA
0AMH18 0060
123.4TFA
336.2FM
232.5FM

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2019-04-18T22:19:15-07:00
documentation
PROPIPE
is_lateral_inspection
false