Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 7, 2016, 06:31 AM
  • B 0698A_B 0698 _06122016_225054.mp4

Date
12/06/2016
W/O
607802
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00110
PipeID
P09369
Time
10:31 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
3844
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_607802_TV22155_DEC2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
B 0698A
Downstream MH
B 0698
Dir. of Survey
Downstream
Length Surveyed
165.4 ft.
Total Length
165.4 ft.
Structural Index
3
Structural Quick
3E22
Structural Rating
97
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
97
Pipe schematic from manhole B 0698A to B 0698
MH: B 0698AMH: B 0698downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 0698A0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area7.9 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start15.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"24.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.5 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES98 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES106.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"163.3 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish165.4 ft. AMH - Downstream Manhole, Survey Ends - B 0698165.4 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK

Observation photos (3)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    7.9 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    95.5 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    98 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

Observations (14)

DistanceCodeObservation
0AMHB 0698A
0MWL
165.4AMHB 0698
15.9TF
24.7TF
106.1TFC
98CL
95.5CL
163.3SAV
159.1TF
7.9SAV
109.2TF
0MWM
165.4MGOCONNECTION AT THE MH 3 O'CLOCK

Properties (6)

additional_info
SC304594
custom_field_two
3
customer
LACSD
datetime
2016-12-06T22:31:18-08:00
documentation
PROPIPE
is_lateral_inspection
false