Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2016, 09:20 AM
  • A 0564_A 0563_20160406_022911.mp4

Date
04/06/2016
W/O
563407
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00327
PipeID
P08345
Time
2:20 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3245
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE, CA 90260
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Routine Assessment
Project
WO_563407_TV05154_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
A 0563
Downstream MH
A 0564
Dir. of Survey
Upstream
Length Surveyed
159.2 ft.
Total Length
159.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole A 0563 to A 0564
MH: A 0563MH: A 0564upstream0 ft. AMH - Upstream Manhole, Survey Ends - A 05640 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"72.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"80.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"154.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start159.2 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK159.2 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK159.2 ft. AMH - Downstream Manhole, Survey Begins - A 0563159.2 ft. MWM - Water Mark, 20 %of cross sectional area159.2 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    78.8 ft. - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    156.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (12)

DistanceCodeObservation
0MGOLATERAL AT MH 9 OCLOCK
0MGOLATERAL AT MH 3 OCLOCK
159.2AMHA 0564
159.2MGOLATERAL AT MH 3 OCLOCK
4.6DAGS
0AMHA 0563
0MWM
78.8TFA
0MWL
156.9DAGS
150.2TFA
86.5TFA

Properties (6)

additional_info
SC305337
custom_field_two
4
customer
LACSD
datetime
2016-04-06T02:20:19-07:00
documentation
PRO-PIPE
is_lateral_inspection
false