Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2016, 05:39 AM
  • A 0571_A 0570_20160405_231144.mp4

Date
04/05/2016
W/O
563407
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00327
PipeID
P08352
Time
10:39 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3245
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE, CA 90260
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
WO_563407_TV05154_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
A 0571
Downstream MH
A 0570
Dir. of Survey
Downstream
Length Surveyed
522.9 ft.
Total Length
522.9 ft.
Structural Index
3
Structural Quick
4132
Structural Rating
16
O&M Index
2
O&M Quick
2T00
O&M Rating
206
Overall Index
2
Overall Quick
Overall Rating
222
Pipe schematic from manhole A 0571 to A 0570
MH: A 0571MH: A 0570downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05710 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK7.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start41.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"42.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES46.5 ft. FM - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: NO46.5 ft. H - Hole, at 01 o'clock, within 8 inches of joint: NO49.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"77.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"79.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: NO101.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"124.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"152.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"160.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"193.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"196.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"198.4 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES245 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"247.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"280.1 ft. MGO - General Observation - ELIMINATED MANHOLE282 ft. MGO - General Observation - ABANDONED LATERAL AT MH 9 OCLOCK282 ft. MGO - General Observation - ABANDONED LATERAL AT MH 3 OCLOCK332 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 6"345.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"368.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"397.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"415.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"448.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"449.8 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: NO456.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"500.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"502.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"520.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish522.9 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK522.9 ft. AMH - Downstream Manhole, Survey Ends - A 0570

Observation photos (12)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    41.3 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    42.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: NO

    46.5 ft. - Fracture Multiple, from 12 to 02 o'clock, within 8 inches of joint: NO

  • Hole, at 01 o'clock, within 8 inches of joint: NO

    46.5 ft. - Hole, at 01 o'clock, within 8 inches of joint: NO

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: NO

    79.2 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: NO

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    198.4 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • General Observation - ELIMINATED MANHOLE

    280.1 ft. - General Observation - ELIMINATED MANHOLE

  • General Observation - ABANDONED LATERAL AT MH 3 OCLOCK

    282 ft. - General Observation - ABANDONED LATERAL AT MH 3 OCLOCK

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: NO

    449.8 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: NO

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    456.7 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    520.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (37)

DistanceCodeObservation
152.3TFC
160.2TFC
345.9TFC
282MGOABANDONED LATERAL AT MH 9 OCLOCK
101.7TFC
456.7TF
193.4TFC
522.9MGOLATERAL AT MH 9 OCLOCK
522.9AMHA 0570
46.5FM
42.2CM
46.5H
500.3TF
415.3TFC
124.4TFC
449.8CL
196.7TFC
247.8TFC
368.6TFC
282MGOABANDONED LATERAL AT MH 3 OCLOCK
77.9TFC
7.2DAGS
0MWL
0MWM
245TFC
0AMHA 0571
448.6TFC
198.4CL
520.1DAGS
397.2TFC
502.9TFC
79.2CL
332TFC
280.1MGOELIMINATED MANHOLE
0MGOLATERAL AT MH 3 OCLOCK
41.3TFC
49.5TFC

Properties (6)

additional_info
SC305337
custom_field_two
4
customer
LACSD
datetime
2016-04-05T22:39:33-07:00
documentation
PRO-PIPE
is_lateral_inspection
false