Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2016, 10:17 AM
  • A 0560_A 0559_20160406_032853.mp4

Date
04/06/2016
W/O
563407
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00327
PipeID
P08341
Time
3:17 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3245
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE, CA 90260
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Routine Assessment
Project
WO_563407_TV05154_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
A 0560
Downstream MH
A 0559
Dir. of Survey
Downstream
Length Surveyed
270 ft.
Total Length
270 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2I00
O&M Rating
104
Overall Index
2
Overall Quick
Overall Rating
104
Pipe schematic from manhole A 0560 to A 0559
MH: A 0560MH: A 0559downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 05600 ft. MGO - General Observation - LATERAL AT MH 8 OCLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK7.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start83 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"106.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"149.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"172.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"199.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"238.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"267.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish270 ft. AMH - Downstream Manhole, Survey Ends - A 0559

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    106.2 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    199.6 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"

Observations (14)

DistanceCodeObservation
0AMHA 0560
267.2DAGS
238.8TF
7.1DAGS
106.2TFC
0MGOLATERAL AT MH 8 OCLOCK
0MWM
199.6TF
0MWL
172.2TFC
83TF
149.1TFA
270AMHA 0559
0MGOLATERAL AT MH 9 OCLOCK

Properties (6)

additional_info
SC305337
custom_field_two
4
customer
LACSD
datetime
2016-04-06T03:17:46-07:00
documentation
PRO-PIPE
is_lateral_inspection
false