Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2016, 05:43 AM
  • A 0550_A 0549_20160420_225959.mp4

Date
04/20/2016
W/O
563407
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00327
PipeID
P08330
Time
10:43 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3322
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Routine Assessment
Project
WO_563407_TV05154_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
A 0550
Downstream MH
A 0549
Dir. of Survey
Downstream
Length Surveyed
356.1 ft.
Total Length
356.1 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
120
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
124
Pipe schematic from manhole A 0550 to A 0549
MH: A 0550MH: A 0549downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05500 ft. MWL - Water Level, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"16.4 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"92.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"123.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES136.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.6 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start175.9 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"190.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"254.7 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"298.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"341.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"349.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish354.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish356.1 ft. AMH - Downstream Manhole, Survey Ends - A 0549

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    123.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    154.6 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0MWM
254.7TFA
0AMHA 0550
92.9TFA
2DAGS
0MWL
154.6CM
298.4TFA
6.6TFA
349.7CM
354.2DAGS
356.1AMHA 0549
136.5TFA
175.9TFA
341.7TFA
190.7TFA
16.4TFA
123.2CM

Properties (6)

additional_info
SC305450
custom_field_two
4
customer
LACSD
datetime
2016-04-20T22:43:24-07:00
documentation
PRO PIPE
is_lateral_inspection
false