Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2016, 06:21 AM
  • A 0548_A 0547_20160420_234637.mp4

Date
04/20/2016
W/O
563407
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00327
PipeID
P08328
Time
11:21 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3322
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
20
Purpose
Routine Assessment
Project
WO_563407_TV05154_APRIL2016
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
A 0548
Downstream MH
A 0547
Dir. of Survey
Downstream
Length Surveyed
394.2 ft.
Total Length
394.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2O00
O&M Rating
158
Overall Index
2
Overall Quick
Overall Rating
158
Pipe schematic from manhole A 0548 to A 0547
MH: A 0548MH: A 0547downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05482 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start146.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"185.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES392 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish394.2 ft. MGO - General Observation - CAPPED CONNECTION AT MH 9 O'CLOCK394.2 ft. AMH - Downstream Manhole, Survey Ends - A 0547394.2 ft. MGO - General Observation - CAPPED CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
0MWL
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
392DAGS
394.2MGOCAPPED CONNECTION AT MH 9 O'CLOCK
394.2AMHA 0547
2DAGS
0MWM
185.9DSZ
0AMHA 0548
146.1TFA
394.2MGOCAPPED CONNECTION AT MH 3 O'CLOCK

Properties (6)

additional_info
SC305450
custom_field_two
4
customer
LACSD
datetime
2016-04-20T23:21:26-07:00
documentation
PRO PIPE
is_lateral_inspection
false