Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 26, 2016, 11:51 AM
  • 05 0157_05 0156_20160126_040141.mp4

Date
01/26/2016
W/O
541742
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00431
PipeID
P05449
Time
3:51 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2782
Sewer Name
05 DISTRICT #5 MAIN TRUNK
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
10
Purpose
Routine Assessment
Project
WO_541742_TV05147_DEC2015
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
05 0157
Downstream MH
05 0156
Dir. of Survey
Downstream
Length Surveyed
331.4 ft.
Total Length
331.4 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 05 0157 to 05 0156
MH: 05 0157MH: 05 0156downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 01570 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 6 OCLOCK2.6 ft. MGO - General Observation - MAG COAT6.9 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start66 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish153.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO331.4 ft. AMH - Downstream Manhole, Survey Ends - 05 0156

Observation photos (2)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    6.9 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  10 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: NO

    153.2 ft. - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO

Observations (10)

DistanceCodeObservation
6.9SAV
66SAV
0AMH05 0157
331.4AMH05 0156
0MWL
0MGOLATERAL AT MH 9 OCLOCK
0MWM
153.2DSZ
0MGOLATERAL AT MH 6 OCLOCK
2.6MGOMAG COAT

Properties (6)

additional_info
SC207094
custom_field_two
4
customer
LACSD
datetime
2016-01-26T03:51:32-08:00
documentation
PROPIPE
is_lateral_inspection
false