Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2016, 11:46 PM
  • H 0667_H 0666_20160714_014929.mp4

Date
06/29/2016
W/O
574527
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00941
PipeID
P11074
Time
4:46 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3613
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
03
Purpose
Routine Assessment
Project
WO_574527_TV18074_JULY2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
28 in.
Width
28 in.
Upstream MH
H 0667
Downstream MH
H 0666
Dir. of Survey
Downstream
Length Surveyed
402.1 ft.
Total Length
402.1 ft.
Structural Index
2
Structural Quick
2O00
Structural Rating
160
O&M Index
2
O&M Quick
2_00
O&M Rating
318
Overall Index
2
Overall Quick
Overall Rating
478
Pipe schematic from manhole H 0667 to H 0666
MH: H 0667MH: H 0666downstream0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LIGHT AMOUNT0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 06670 ft. MGO - General Observation - MAG COATING 85%5.1 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - OTHER400 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish400 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - OTHER400 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish402.1 ft. AMH - Downstream Manhole, Survey Ends - H 0666 RUN LIST STATES MH AT 496'

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LIGHT AMOUNT

    0 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - LIGHT AMOUNT

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Settled Other,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start - OTHER

    5.1 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - OTHER

Observations (11)

DistanceCodeObservation
0SSSLIGHT AMOUNT
400SSS
0MWL
402.1AMHH 0666 RUN LIST STATES MH AT 496'
400DSZOTHER
0DAGS
0MWM
0AMHH 0667
0MGOMAG COATING 85%
5.1DSZOTHER
400DAGS

Properties (6)

additional_info
SC305792
custom_field_two
3
customer
LACSD
datetime
2016-06-29T16:46:40-07:00
documentation
PROPIPE
is_lateral_inspection
false