Wastewater/Activity/PacpInspection/1.0Jun 29, 2016, 11:46 PM
  • H 0665_H 0664 _20160714_034303.mp4

Date
06/29/2016
W/O
574527
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00941
PipeID
P11072
Time
4:46 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3613
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
03
Purpose
Routine Assessment
Project
WO_574527_TV18074_JULY2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
28 in.
Width
28 in.
Upstream MH
H 0665
Downstream MH
H 0664
Dir. of Survey
Downstream
Length Surveyed
505.4 ft.
Total Length
505.4 ft.
Structural Index
3
Structural Quick
3S2S
Structural Rating
500
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
502
Pipe schematic from manhole H 0665 to H 0664
MH: H 0665MH: H 0664downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 06650 ft. MWL - Water Level, 35 %of cross sectional area1.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start1.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start1.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start503.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish503.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish503.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish505.4 ft. AMH - Downstream Manhole, Survey Ends - H 0664

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    1.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    1.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    1.1 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
1.1DAGS
503.1SSS
505.4AMHH 0664
0MWM
503.1DAGS
503.1SAV
1.1SSS
1.1SAV
0AMHH 0665
0MWL

Properties (6)

additional_info
SC305792
custom_field_two
3
customer
LACSD
datetime
2016-06-29T16:46:39-07:00
documentation
PROPIPE
is_lateral_inspection
false