Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2016, 11:46 PM
  • H 0673_H 0672_20160713_033755.mp4

Date
06/29/2016
W/O
574527
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00941
PipeID
P11080
Time
4:46 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3612
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
03
Purpose
Routine Assessment
Project
WO_574527_TV18074_JULY2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0672
Downstream MH
H 0673
Dir. of Survey
Upstream
Length Surveyed
595.8 ft.
Total Length
595.8 ft.
Structural Index
3
Structural Quick
3W2W
Structural Rating
595
O&M Index
3
O&M Quick
413A
O&M Rating
34
Overall Index
3
Overall Quick
Overall Rating
629
Pipe schematic from manhole H 0672 to H 0673
MH: H 0672MH: H 0673upstream0 ft. AMH - Upstream Manhole, Survey Ends - H 06731.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish4.7 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish - OTHER51.7 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - OTHER96.8 ft. DSZ - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - OTHER595.8 ft. AMH - Downstream Manhole, Survey Begins - H 0672595.8 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start595.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start595.8 ft. MWL - Water Level, 40 %of cross sectional area595.8 ft. MWM - Water Mark, 50 %of cross sectional area

Observation photos (4)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    0 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    0 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  15 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES - OTHER

    499 ft. - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - OTHER

  • Deposits Settled Other,  15 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start - OTHER

    544.1 ft. - Deposits Settled Other, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start - OTHER

Observations (11)

DistanceCodeObservation
0AMHH 0672
0SAV
0SSS
594.1SSS
499DSZOTHER
594.1SAV
595.8AMHH 0673
0MWL
591.1DSZOTHER
544.1DSZOTHER
0MWM

Properties (6)

additional_info
SC305791
custom_field_two
2
customer
LACSD
datetime
2016-06-29T16:46:42-07:00
documentation
PROPIPE
is_lateral_inspection
false