Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 29, 2016, 11:46 PM
  • H 0669_H 0668_20160714_012902.mp4

Date
06/29/2016
W/O
574527
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00941
PipeID
P11076
Time
4:46 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3613
Sewer Name
H JOINT OUTFALL H - UNIT 9B
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
03
Purpose
Routine Assessment
Project
WO_574527_TV18074_JULY2016
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
25 in.
Width
25 in.
Upstream MH
H 0669
Downstream MH
H 0668
Dir. of Survey
Downstream
Length Surveyed
936.7 ft.
Total Length
936.7 ft.
Structural Index
2
Structural Quick
2d00
Structural Rating
374
O&M Index
2
O&M Quick
2n00
O&M Rating
466
Overall Index
2
Overall Quick
Overall Rating
840
Pipe schematic from manhole H 0669 to H 0668
MH: H 0669MH: H 0668downstream0 ft. MGO - General Observation - MAG COATING 75%0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start0 ft. AMH - Upstream Manhole, Survey Begins - H 0669386 ft. MGO - General Observation - ABANDONED MH423 ft. MGO - General Observation - ABANDONED MH563.1 ft. MGO - General Observation - RUN LIST STATES MH AT 562'705.1 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - OTHER936.1 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish - OTHER936.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish936.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish936.7 ft. AMH - Downstream Manhole, Survey Ends - H 0668

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    0 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ABANDONED MH

    386 ft. - General Observation - ABANDONED MH

  • General Observation - ABANDONED MH

    423 ft. - General Observation - ABANDONED MH

  • Deposits Settled Other,  10 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start - OTHER

    705.1 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - OTHER

Observations (14)

DistanceCodeObservation
936.1DSZOTHER
936.1SSS
0MGOMAG COATING 75%
0MWL
0MWM
563.1MGORUN LIST STATES MH AT 562'
936.1DAGS
423MGOABANDONED MH
936.7AMHH 0668
0DAGS
0SSS
0AMHH 0669
386MGOABANDONED MH
705.1DSZOTHER

Properties (6)

additional_info
SC305792
custom_field_two
3
customer
LACSD
datetime
2016-06-29T16:46:41-07:00
documentation
PROPIPE
is_lateral_inspection
false