Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 18, 2016, 07:03 AM
  • 18 0419_18 0418_20160318_002004.mp4

Date
03/18/2016
W/O
557858
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00699
PipeID
P14254
Time
12:03 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3228
Sewer Name
18 SANTA FE STREET RELIEF TRUNK
City
WHITTIER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
WO_557858_TV18044_2016MAR
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
18 in.
Upstream MH
18 0419
Downstream MH
18 0418
Dir. of Survey
Downstream
Length Surveyed
354.8 ft.
Total Length
354.8 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
210
O&M Index
3
O&M Quick
4122
O&M Rating
8
Overall Index
3
Overall Quick
Overall Rating
218
Pipe schematic from manhole 18 0419 to 18 0418
MH: 18 0419MH: 18 0418downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 04190 ft. MWL - Water Level, 40 %of cross sectional area0 ft. MWM - Water Mark, 65 %of cross sectional area2 ft. MGO - General Observation - MAGNEZIUM H.O. START 50%2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start5.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start352 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish352.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish354.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0418

Observation photos (2)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    5.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
2MGOMAGNEZIUM H.O. START 50%
352.2DAGS
2SAV
354.8AMH18 0418
0AMH18 0419
0MWL
352SAV
5.1DAGS
0MWM

Properties (6)

additional_info
SC305319
custom_field_two
3
customer
LACSD
datetime
2016-03-18T00:03:26-07:00
documentation
PRO-PIPE
is_lateral_inspection
false