Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2016, 12:41 PM
  • 05 0768_05 0767_14032016_054147.mp4

Date
03/14/2016
W/O
557677
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00553
PipeID
P05995
Time
5:41 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3288
Sewer Name
05 MANCHESTER-VERMONT DIVERSION EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_557677_TV05272_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 0768
Downstream MH
05 0767
Dir. of Survey
Downstream
Length Surveyed
413.8 ft.
Total Length
413.8 ft.
Structural Index
4
Structural Quick
4O00
Structural Rating
324
O&M Index
2
O&M Quick
2`00
O&M Rating
328
Overall Index
3
Overall Quick
Overall Rating
652
Pipe schematic from manhole 05 0768 to 05 0767
MH: 05 0768MH: 05 0767downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 07680 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start410.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish411.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish411.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish413.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0767

Observation photos (3)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
411.9DAE
2DAE
0AMH05 0768
411.9DAGS
413.8AMH05 0767
6.1FM
0MWM
2DAGS
410.1FM
0MWL

Properties (6)

additional_info
SC305412
custom_field_two
2
customer
LACSD
datetime
2016-03-14T05:41:14-07:00
documentation
PRO PIPE
is_lateral_inspection
false