Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 14, 2016, 07:56 AM
  • 05 0779_05 0778_14032016_005827.mp4

Date
03/14/2016
W/O
557677
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00553
PipeID
P06007
Time
12:56 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3288
Sewer Name
05 MANCHESTER-VERMONT DIVERSION EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_557677_TV05272_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
05 0779
Downstream MH
05 0778
Dir. of Survey
Downstream
Length Surveyed
387 ft.
Total Length
387 ft.
Structural Index
3
Structural Quick
4G3L
Structural Rating
347
O&M Index
2
O&M Quick
2^00
O&M Rating
308
Overall Index
3
Overall Quick
Overall Rating
655
Pipe schematic from manhole 05 0779 to 05 0778
MH: 05 0779MH: 05 0778downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 07790 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start37.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES46.3 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES67.6 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start146.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES166.4 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES195 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES211 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start385.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish385.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish385.1 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish385.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish387 ft. AMH - Downstream Manhole, Survey Ends - 05 0778

Observation photos (9)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES

    37.6 ft. - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

    46.3 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    67.6 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    146.1 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    166.4 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    195 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    211 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
385.1FM
166.4FM
2DAE
2DAGS
146.1FM
387AMH05 0778
46.3FM
211FM
0MWM
385.1DAE
0AMH05 0779
385.1CM
37.6FC
195FM
0MWL
385.1DAGS
67.6CM

Properties (6)

additional_info
SC305412
custom_field_two
2
customer
LACSD
datetime
2016-03-14T00:56:45-07:00
documentation
PRO PIPE
is_lateral_inspection
false