Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 8, 2016, 07:44 AM
  • 08 0580_08 0109_07032016_234423.mp4

Date
03/07/2016
W/O
557595
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00015
PipeID
P00159
Time
11:44 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3279
Sewer Name
08 MAIN STREET RELIEF TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_557595_TV08024_2016MAR
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
08 0580
Downstream MH
08 0109
Dir. of Survey
Downstream
Length Surveyed
113.1 ft.
Total Length
113.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2C00
O&M Rating
44
Overall Index
2
Overall Quick
Overall Rating
44
Pipe schematic from manhole 08 0580 to 08 0109
MH: 08 0580MH: 08 0109downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 05800 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING 60%111.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish113.1 ft. AMH - Downstream Manhole, Survey Ends - 08 0109

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWM
2DAGS
113.1AMH08 0109
2MGOMAG COATING 60%
111.5DAGS
0AMH08 0580
0MWL

Properties (6)

additional_info
SC305403
custom_field_two
4
customer
LACSD
datetime
2016-03-07T23:44:08-08:00
documentation
PRO PIPE
is_lateral_inspection
false