Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2016, 08:27 AM
  • 01 1347_01 1346_10032016_002754.mp4

Date
03/10/2016
W/O
557557
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00207
PipeID
P18919
Time
12:27 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3281
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE RELIEF TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_557557_TV01128_2016MAR
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
21 in.
Upstream MH
01 1346
Downstream MH
01 1347
Dir. of Survey
Upstream
Length Surveyed
292.9 ft.
Total Length
292.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
2
Overall Quick
Overall Rating
116
Pipe schematic from manhole 01 1346 to 01 1347
MH: 01 1346MH: 01 1347upstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Ends - 01 13470.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish25.3 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"75.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"107.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"140.4 ft. TFA - Tap Factory Made Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"191.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"227.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"290.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start292.9 ft. AMH - Downstream Manhole, Survey Begins - 01 1346292.9 ft. MWM - Water Mark, 20 %of cross sectional area292.9 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    292.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
185.5TFA
292.9MGOCOCKROACHES IN MANHOLE
217.2TFA
2DAGS
101.8TFA
0AMH01 1346
152.5TFA
292.9AMH01 1347
0MWM
292.1DAGS
0MWL
267.6TFA
65.1TFC

Properties (7)

additional_info
SC305405
custom_field_two
4
customer
LACSD
datetime
2016-03-10T00:27:13-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
19921017