Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2016, 10:05 AM
  • 05 1603_05 1602_11032016_020636.mp4

Date
03/11/2016
W/O
557657
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00551
PipeID
P06827
Time
2:05 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3285
Sewer Name
05 203RD STREET TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_557657_TV05176_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1603
Downstream MH
05 1602
Dir. of Survey
Downstream
Length Surveyed
295.8 ft.
Total Length
295.8 ft.
Structural Index
4
Structural Quick
4E21
Structural Rating
130
O&M Index
2
O&M Quick
2K00
O&M Rating
120
Overall Index
3
Overall Quick
Overall Rating
250
Pipe schematic from manhole 05 1603 to 05 1602
MH: 05 1603MH: 05 1602downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 16020 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start51.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"103.4 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"155.7 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"163.4 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish211.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"254.1 ft. RFB - Roots Fine Barrell, at 11 o'clock, within 8 inches of joint: YES254.1 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES267.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"295.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE295.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish295.8 ft. AMH - Downstream Manhole, Survey Ends - 05 1602

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Barrell, at 11 o'clock, within 8 inches of joint: YES

    254.1 ft. - Roots Fine Barrell, at 11 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    254.1 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    295.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (17)

DistanceCodeObservation
103.4TFA
295.1MGOCOCKROACHES IN MANHOLE
163.4FH2
0MWM
254.1RFB
51.7TFA
254.1CL
0AMH05 1602
155.7TFA
0MWL
2FH2
0MGOCOCKROACHES IN MANHOLE
295.8AMH05 1602
267.3TFA
211.5TFA
2DAGS
295.1DAGS

Properties (6)

additional_info
SC305409
custom_field_two
2
customer
LACSD
datetime
2016-03-11T02:05:42-08:00
documentation
PRO PIPE
is_lateral_inspection
false