Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2016, 09:53 AM
  • 05 1604_05 1603_11032016_015343.mp4

Date
03/11/2016
W/O
557657
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00551
PipeID
P06828
Time
1:53 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3285
Sewer Name
05 203RD STREET TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_557657_TV05176_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1604
Downstream MH
05 1603
Dir. of Survey
Downstream
Length Surveyed
299.2 ft.
Total Length
299.2 ft.
Structural Index
4
Structural Quick
4J00
Structural Rating
224
O&M Index
2
O&M Quick
2K00
O&M Rating
120
Overall Index
3
Overall Quick
Overall Rating
344
Pipe schematic from manhole 05 1604 to 05 1603
MH: 05 1604MH: 05 1603downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 16040 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area2 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start23 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"59.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"112.2 ft. TBI - Tap Break-In Intruding, at 12 o'clock, -, #v, within 8 inches of joint: NO, 6", 1"274.7 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"281.4 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish296.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish299.2 ft. AMH - Downstream Manhole, Survey Ends - 05 1603299.2 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 12 o'clock, -, #v, within 8 inches of joint: NO, 6", 1"

    112.2 ft. - Tap Break-In Intruding, at 12 o'clock, -, #v, within 8 inches of joint: NO, 6", 1"

  • General Observation - COCKROACHES IN MANHOLE

    299.2 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
281.4FH2
274.7TF
2FH2
296.6DAGS
0AMH05 1604
0MWM
2DAGS
112.2TBI
0MWL
59.6TF
23TBA
299.2AMH05 1603
299.2MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC305409
custom_field_two
2
customer
LACSD
datetime
2016-03-11T01:53:25-08:00
documentation
PRO PIPE
is_lateral_inspection
false