Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2016, 09:34 AM
  • 05 1605_05 1604_11032016_013500.mp4

Date
03/11/2016
W/O
557657
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00551
PipeID
P06829
Time
1:34 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3285
Sewer Name
05 203RD STREET TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_557657_TV05176_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
05 1605
Downstream MH
05 1604
Dir. of Survey
Downstream
Length Surveyed
298.3 ft.
Total Length
298.3 ft.
Structural Index
4
Structural Quick
4K00
Structural Rating
236
O&M Index
2
O&M Quick
312K
O&M Rating
122
Overall Index
3
Overall Quick
Overall Rating
358
Pipe schematic from manhole 05 1605 to 05 1604
MH: 05 1605MH: 05 1604downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 16050 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start2 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start14.3 ft. TBD - Tap Break-In Defective, at 12 o'clock, -, , within 8 inches of joint: YES, 6" - ROOTS AT CONNECTIOIN14.3 ft. RFC - Roots Fine Connection, from 11 to 01 o'clock, within 8 inches of joint: YES46.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"91.4 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"98.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"156.9 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"190.5 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"214.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"273.9 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"296.5 ft. FH2 - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish296.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish296.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE298.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1604

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Fracture Longitudinal Hinge, 2, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Connection, from 11 to 01 o'clock, within 8 inches of joint: YES

    14.3 ft. - Roots Fine Connection, from 11 to 01 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    296.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (18)

DistanceCodeObservation
0MWM
46.8TFA
98.6TFA
2DAGS
14.3TBDROOTS AT CONNECTIOIN
296.5FH2
91.4TBA
298.3AMH05 1604
273.9TBA
296.5DAGS
214.5TFA
0AMH05 1605
2FH2
0MWL
14.3RFC
296.5MGOCOCKROACHES IN MANHOLE
190.5TBA
156.9TBA

Properties (6)

additional_info
SC305409
custom_field_two
2
customer
LACSD
datetime
2016-03-11T01:34:45-08:00
documentation
PRO PIPE
is_lateral_inspection
false