Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 18, 2015, 11:19 AM
  • 03 0314_03 0313_20151218_033337.mp4

Date
12/18/2015
W/O
531067
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00359
PipeID
P04888
Time
3:19 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2894
Sewer Name
03 ANAHEIM STREET TRUNK
City
LONG BEACH, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_531067_TV03106_DEC2015
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
30 in.
Upstream MH
03 0314
Downstream MH
03 0313
Dir. of Survey
Downstream
Length Surveyed
335.6 ft.
Total Length
335.6 ft.
Structural Index
3
Structural Quick
4L2L
Structural Rating
390
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
395
Pipe schematic from manhole 03 0314 to 03 0313
MH: 03 0314MH: 03 0313downstream0 ft. MWL - Water Level, 70 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 03140 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 9 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MANHOLE ACTIVE 3 O'CLOCK0 ft. MWM - Water Mark, 80 %of cross sectional area2 ft. MGO - General Observation - BEGIN MAGNESIUM HYDROXIDE COATING7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start7 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start332.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish332.8 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish335.6 ft. AMH - Downstream Manhole, Survey Ends - 03 0313

Observation photos (3)

  • General Observation - BEGIN MAGNESIUM HYDROXIDE COATING

    2 ft. - General Observation - BEGIN MAGNESIUM HYDROXIDE COATING

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    7 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWL
332.8SAM
0AMH03 0314
332.7SSS
2MGOBEGIN MAGNESIUM HYDROXIDE COATING
335.6AMH03 0313
7SSS
0MGOCONNECTION AT MANHOLE ACTIVE 9 O'CLOCK
0MGOCONNECTION AT MANHOLE ACTIVE 3 O'CLOCK
0MWM
7SAM

Properties (6)

additional_info
SC224472
custom_field_two
3
customer
LACSD
datetime
2015-12-18T03:19:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false