Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 25, 2016, 11:03 AM
  • 03 0303A_03 0303_20160125_032707.mp4

Date
01/25/2016
W/O
531067
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00359
PipeID
P05156
Time
3:03 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3124
Sewer Name
03 ANAHEIM STREET TRUNK
City
LONG BEACH, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_531067_TV03106_DEC2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Lining Method
Segmented Panel
Shape
Circular
Height
39 in.
Upstream MH
03 0303A
Downstream MH
03 0303
Dir. of Survey
Downstream
Length Surveyed
597.5 ft.
Total Length
597.5 ft.
Structural Index
2
Structural Quick
2200
Structural Rating
4
O&M Index
2
O&M Quick
4123
O&M Rating
11
Overall Index
2
Overall Quick
Overall Rating
15
Pipe schematic from manhole 03 0303A to 03 0303
MH: 03 0303AMH: 03 0303downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03 0303A0 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK24.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start104.2 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - WANDERING212.3 ft. CS - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish225.5 ft. TFD - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS225.6 ft. RMB - Roots Medium Barrell, at 12 o'clock, 10 %, within 8 inches of joint: NO593.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish595.6 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK595.7 ft. VC - Vermin Cockroach597.5 ft. AMH - Downstream Manhole, Survey Ends - 03 0303

Observation photos (4)

  • Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - WANDERING

    104.2 ft. - Crack Spiral, from 11 to 01 o'clock, within 8 inches of joint: YES, Start - WANDERING

  • Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    225.5 ft. - Tap Factory Made Defective, at 12 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

  • Roots Medium Barrell, at 12 o'clock, 10 %, within 8 inches of joint: NO

    225.6 ft. - Roots Medium Barrell, at 12 o'clock, 10 %, within 8 inches of joint: NO

  • Vermin Cockroach

    595.7 ft. - Vermin Cockroach

Observations (13)

DistanceCodeObservation
212.3CS
0MWL
595.6MGOLATERAL AT MH 3 OCLOCK
225.5TFDROOTS
0MWM
593.1DAGS
597.5AMH03 0303
0AMH03 0303A
225.6RMB
24.1DAGS
104.2CSWANDERING
595.7VC
0MGOLATERAL AT MH 9 OCLOCK

Properties (6)

additional_info
SC225509
custom_field_two
3
customer
LACSD
datetime
2016-01-25T03:03:00-08:00
documentation
PRO-PIPE
is_lateral_inspection
false