Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2017, 06:17 AM
  • 32 0132A_32 0132_14092017_232742.mp4

Date
09/14/2017
W/O
658035
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00887
PipeID
P19880
Time
11:17 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4875
Sewer Name
32 DISTRICT #32 MAIN TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_658035_TV32048_SEP2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 0132A
Downstream MH
32 0132
Dir. of Survey
Downstream
Length Surveyed
403.6 ft.
Total Length
403.6 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
398
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
398
Pipe schematic from manhole 32 0132A to 32 0132
MH: 32 0132AMH: 32 0132downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 32 0132A0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.2 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start6.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start403.6 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish403.6 ft. AMH - Downstream Manhole, Survey Ends - 32 0132403.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK
403.6SAP
2.2SAP
0AMH32 0132A
0MWM
403.6AMH32 0132
403.6SSS
6.1SSS
0MWL

Properties (6)

additional_info
SC345934
custom_field_two
2
customer
LACSD
datetime
2017-09-14T23:17:06-07:00
documentation
PROPIPE
is_lateral_inspection
false