Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2017, 09:12 AM
  • 32 1191_32 1190 _15092017_021226.mp4

Date
09/15/2017
W/O
651642
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00843
PipeID
P19645
Time
2:12 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Media Label
K4877
Sewer Name
32 SOLEDAD CANYON RELIEF TRUNK
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
09
Purpose
Routine Assessment
Project
WO_651642_TV32001_AUG2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
32 1191
Downstream MH
32 1190
Dir. of Survey
Downstream
Length Surveyed
122.9 ft.
Total Length
122.9 ft.
Structural Index
3
Structural Quick
513C
Structural Rating
94
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
94
Pipe schematic from manhole 32 1191 to 32 1190
MH: 32 1191MH: 32 1190downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 6 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 32 11910 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 25 %of cross sectional area16.2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start56.3 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES, Start76.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish76.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start115.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES122.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK122.9 ft. AMH - Downstream Manhole, Survey Ends - 32 1190122.9 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish122.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (4)

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    16.2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    56.3 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    76.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

    115.5 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
122.9MGOCONNECTION AT MH 3 O'CLOCK
76.6SAV
122.9AMH32 1190
0MWL
56.3SSS
0MGOCONNECTION AT MH 6 O'CLOCK
0MGOCONNECTION AT MH 9 O'CLOCK
0AMH32 1191
115.5SRV
0MGOCONNECTION AT MH 3 O'CLOCK
122.9SSS
76.6SAP
122.9SAP
0MWM
16.2SAV

Properties (7)

additional_info
SC345936
custom_field_two
2
customer
LACSD
datetime
2017-09-15T02:12:11-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
26872