Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2015, 06:46 AM
  • 14 0063_14 0062_14042015_011216.mp4

Date
04/13/2015
W/O
497182
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00577
PipeID
P18075
Time
11:46 PM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2468
Sewer Name
14 TRUNK "A"
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
04
Purpose
Routine Assessment
Project
WO_497182_TV14018_2015MARCH
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Upstream MH
14 0063
Downstream MH
14 0062
Dir. of Survey
Downstream
Length Surveyed
438.5 ft.
Total Length
438.5 ft.
Structural Index
3
Structural Quick
3B00
Structural Rating
42
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
46
Pipe schematic from manhole 14 0063 to 14 0062
MH: 14 0063MH: 14 0062downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 00630 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area2 ft. MGO - General Observation - Magnesium hydroxide coating 30% start129.1 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES291 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"341 ft. SAV - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES376.6 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start436.1 ft. MGO - General Observation - Magnesium hydroxide coating 30% finish436.1 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish438.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0062

Observation photos (3)

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES

    129.1 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES

    341 ft. - Surface Aggregate Visible, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    376.6 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0AMH14 0063
438.5AMH14 0062
436.1MGOMagnesium hydroxide coating 30% finish
436.1SAV
291TFC
376.6SAV
341SAV
2MGOMagnesium hydroxide coating 30% start
0MWL
129.1SAV
0MWM

Properties (6)

additional_info
SC201204
custom_field_two
3
customer
LACSD
datetime
2015-04-13T23:46:09-07:00
documentation
PRO PIPE
is_lateral_inspection
false