Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 27, 2017, 06:55 AM
  • B 1195_B 1194_26092017_235634.mp4

Date
09/26/2017
W/O
663486
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z01125
PipeID
P13515
Time
11:55 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4278
Sewer Name
B JOINT OUTFALL B - UNIT 6H
City
S.PASADENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
16
Purpose
Routine Assessment
Project
WO_663486_TV16065_OCT2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
B 1195
Downstream MH
B 1194
Dir. of Survey
Downstream
Length Surveyed
254.2 ft.
Total Length
254.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2A12
O&M Rating
22
Overall Index
2
Overall Quick
Overall Rating
22
Pipe schematic from manhole B 1195 to B 1194
MH: B 1195MH: B 1194downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. VC - Vermin Cockroach0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 11952.3 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start18 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES58.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 12 o'clock, , within 8 inches of joint: YES99 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES195.9 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start215 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish236.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES248.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES250 ft. MGO - General Observation - SPALLING THROUGHOUT THE REACH250.7 ft. DAGS - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish251 ft. MGO - General Observation - SPALLING THROUGHOUT THE REACH254.2 ft. VC - Vermin Cockroach254.2 ft. AMH - Downstream Manhole, Survey Ends - B 1194

Observation photos (7)

  • Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES

    18 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 12 o'clock,  , within 8 inches of joint: YES

    58.5 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 12 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    99 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    195.9 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    236.4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    248.4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
250.7DAGS
254.2VC
248.4DAE
236.4DAE
0MWL
0VC
18DAE
250MGOSPALLING THROUGHOUT THE REACH
0MWM
0AMHB 1195
254.2AMHB 1194
195.9DAE
99DAE
215DAE
251MGOSPALLING THROUGHOUT THE REACH
2.3DAGS
58.5DAE

Properties (6)

additional_info
SC352125
custom_field_two
3
customer
LACSD
datetime
2017-09-26T23:55:20-07:00
documentation
PRO PIPE
is_lateral_inspection
false