Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 10, 2017, 05:05 AM
  • 02 1826_02 1981 _09102017_220503.mpg

Date
10/09/2017
W/O
663355
Weather
Dry
Operator/Surveyor
ERU
Sewer ID
Z00236
PipeID
P04175
Time
10:05 PM
Certificate
123456
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K5106
Sewer Name
02 ATLANTIC AVENUE RELIEF TRUNK
City
EAST LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_663355_TV02017_OCT2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1826
Downstream MH
02 1981
Dir. of Survey
Downstream
Length Surveyed
31.3 ft.
Total Length
31.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 02 1826 to 02 1981
MH: 02 1826MH: 02 1981downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins0 ft. MWL - Water Level, 25 %of cross sectional area5.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start25.6 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish28.2 ft. MWM - Water Mark, 40 %of cross sectional area28.2 ft. MGO - General Observation - CONNECTION AT MH AT 9 OCLOCK28.2 ft. MWL - Water Level, 40 %of cross sectional area31.3 ft. AMH - Downstream Manhole, Survey Ends

Observation photos (1)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.9 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
28.2MWM
0MWM
28.2MGOCONNECTION AT MH AT 9 OCLOCK
0AMH
0MWL
5.9SAP
25.6SAP
31.3AMH
28.2MWL

Properties (5)

custom_field_two
CR3
customer
LACSD
datetime
2017-10-09T22:05:00-07:00
documentation
PROPIPE
is_lateral_inspection
false