Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 27, 2017, 08:46 AM
  • 05 1714_05 1713_11272017_012215.mp4

Date
11/27/2017
W/O
0674089
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00471
PipeID
P06941
Time
12:46 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0683
Sewer Name
05 LOMITA TRUNK
City
LOMITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
33
Purpose
Capital Improvement Program Assesment
Project
20171127MDM_LOMITA_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
05 1714
Downstream MH
05 1713
Dir. of Survey
Downstream
Length Surveyed
286.7 ft.
Total Length
286.7 ft.
Structural Index
2
Structural Quick
352B
Structural Rating
43
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
45
Pipe schematic from manhole 05 1714 to 05 1713
MH: 05 1714MH: 05 1713downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM6 ft. FS - Fracture Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT6 ft. FS - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES, Start - SLIGHT12.9 ft. MGO - General Observation - 21" ,VCP32.4 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL47.4 ft. FC - Fracture Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES - HAIRLINE50.5 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H71.4 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL81.3 ft. FS - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES - SLIGHT81.3 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H114 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - H117.3 ft. FS - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: NO - SL118 ft. FS - Fracture Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES - SL132.2 ft. FC - Fracture Circumferential, from 08 to 12 o'clock, within 8 inches of joint: YES - SL132.2 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL135.7 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H141.5 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H147.5 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES - BRICK PICIES159.9 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SL171.9 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H220.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL229.5 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H251.5 ft. MGP - General Photograph - SLIGHT SPRIALS286.2 ft. FS - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES, Finish - SLIGHT286.2 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. OPEN286.2 ft. FS - Fracture Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES, Finish - SLIGHT286.7 ft. AMH - Downstream Manhole, Survey Ends - 1:35AM

Observation photos (7)

  • Fracture Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    6 ft. - Fracture Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES, Start - SLIGHT

    6 ft. - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES, Start - SLIGHT

  • General Observation - 21" ,VCP

    12.9 ft. - General Observation - 21" ,VCP

  • Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES - SLIGHT

    81.3 ft. - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES - SLIGHT

  • Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: NO - SL

    117.3 ft. - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: NO - SL

  • Fracture Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES - SL

    118 ft. - Fracture Spiral, from 01 to 05 o'clock, within 8 inches of joint: YES - SL

  • General Photograph - SLIGHT SPRIALS

    251.5 ft. - General Photograph - SLIGHT SPRIALS

Observations (29)

DistanceCodeObservation
220.1FCSL
114FCH
0MWM
286.2FSSLIGHT
71.4FCSL
32.4FCSL
6FSSLIGHT
132.2FCSL
81.3FSSLIGHT
159.9FCSL
12.9MGO21" ,VCP
286.2MGOConn. @ Mh, 3 O' Clock. OPEN
6FSSLIGHT
135.7FCH
117.3FSSL
0MWL
251.5MGPSLIGHT SPRIALS
81.3FCH
141.5FCH
286.2FSSLIGHT
171.9FCH
0AMH12:55AM
147.5DSZBRICK PICIES
286.7AMH1:35AM
47.4FCHAIRLINE
118FSSL
229.5FCH
50.5FCH
132.2FCSL

Properties (6)

custom_field_three
SLIGHT SPRIAL FRACTURE JOINT TO JOINT LONGER
custom_field_two
2
customer
LACSD
datetime
2017-11-27T00:46:12-08:00
documentation
MARTIN,REVELES,OLIVER 111
is_lateral_inspection
false