Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 18, 2017, 09:03 AM
  • Section#1_B 0013_B 0012__11182017__G6869.mp2

Date
11/18/2017
W/O
0672781
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00072
PipeID
P08523
Time
1:03 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G6869
Sewer Name
B JOINT OUTFALL B - UNIT 1A
City
CARSON
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
14
Purpose
Capital Improvement Program Assesment
Project
20171118MDM_JOINT_OUTFALL_B_UNIT_1A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
144 in.
Upstream MH
B 0013
Downstream MH
B 0012
Dir. of Survey
Downstream
Length Surveyed
1063.2 ft.
Total Length
1063.2 ft.
Structural Index
5
Structural Quick
5j4i
Structural Rating
1928
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
5
Overall Quick
Overall Rating
1932
Pipe schematic from manhole B 0013 to B 0012
MH: B 0013MH: B 0012downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:50AM0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 50 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR2 ft. MGO - General Observation - 100% MAG COAT 9:00 TO 3:00 START26.8 ft. SRV - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT177.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT177.2 ft. MGO - General Observation - 100% MAG COAT500.3 ft. MGO - General Observation - 11% MAG COAT564.7 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT747.2 ft. SRV - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR833.7 ft. MGP - General Photograph1063.2 ft. AMH - Downstream Manhole, Survey Ends - 2:50AM1063.2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG UNDERE MAG COAT1063.2 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - CIRCUM REBAR UNDER MAG COAT

Observation photos (10)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG UNDER MAG COAT

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

    2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - CIRCUM REBAR

  • General Observation - 100% MAG COAT 9:00 TO 3:00 START

    2 ft. - General Observation - 100% MAG COAT 9:00 TO 3:00 START

  • Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

    26.8 ft. - Surface Reinforcement Visible, from 11 to 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

    177.2 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

  • General Observation - 100% MAG COAT

    177.2 ft. - General Observation - 100% MAG COAT

  • General Observation - 11% MAG COAT

    500.3 ft. - General Observation - 11% MAG COAT

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

    564.7 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR UNDER MAG COAT

  • Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    747.2 ft. - Surface Reinforcement Visible, at 12 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Photograph

    833.7 ft. - General Photograph

Observations (16)

DistanceCodeObservation
747.2SRVCIRCUM REBAR
1063.2AMH2:50AM
177.2SRVCIRCUM REBAR UNDER MAG COAT
26.8SRVCIRCUM REBAR UNDER MAG COAT
500.3MGO11% MAG COAT
1063.2SAMSEVERE AGG UNDERE MAG COAT
564.7SRVCIRCUM REBAR UNDER MAG COAT
833.7MGP
2SAMSEVERE AGG UNDER MAG COAT
177.2MGO100% MAG COAT
0AMH1:50AM
1063.2SRVCIRCUM REBAR UNDER MAG COAT
2SRVCIRCUM REBAR
0MWM
2MGO100% MAG COAT 9:00 TO 3:00 START
0MWL

Properties (7)

custom_field_three
CIRCUM REBAR VISIBLE UNDER 100% MAG COAT
custom_field_two
2
customer
LACSD
datetime
2017-11-18T01:03:18-08:00
documentation
MARTIN,MANANES,REVELES,OLIVER 111
is_lateral_inspection
false
year_laid
20010208