Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 6, 2018, 05:49 AM
  • 32 1134_32 1133 _06042018_003936.mp4

Date
04/05/2018
W/O
696297
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00842
PipeID
P19585
Time
10:49 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5562
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTION 5
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
11
Purpose
Routine Assessment
Project
WO_696297_TV32029_APR2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
32 1134
Downstream MH
32 1133
Dir. of Survey
Downstream
Length Surveyed
99.7 ft.
Total Length
99.7 ft.
Structural Index
3
Structural Quick
513A
Structural Rating
37
O&M Index
2
O&M Quick
412B
O&M Rating
30
Overall Index
3
Overall Quick
Overall Rating
67
Pipe schematic from manhole 32 1134 to 32 1133
MH: 32 1134MH: 32 1133downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 32 11340 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area3 ft. B - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES33 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start38.8 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES50.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start99.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish99.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish99.7 ft. AMH - Downstream Manhole, Survey Ends - 32 1133

Observation photos (4)

  • Broken, from 09 to 03 o'clock, within 8 inches of joint: YES

    3 ft. - Broken, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    33 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    38.8 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    50.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
33DAGS
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
99.7DAGS
38.8CL
0AMH32 1134
99.7CM
99.7AMH32 1133
0MWL
0MWM
50.8CM
3B

Properties (6)

additional_info
SC358521
custom_field_two
2
customer
LACSD
datetime
2018-04-05T22:49:47-07:00
documentation
PRO PIPE
is_lateral_inspection
false