Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 26, 2015, 01:57 PM
  • 02 1109_02 1407_20151026_071341.mp4

Date
10/26/2015
W/O
521067
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00300
PipeID
P03683
Time
6:57 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K2814
Sewer Name
02 RANDOLPH STREET TRUNK
City
COMMERCE
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
WO_521067_TV02229_AUG2015
Sewer Type
GRAVITY
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
02 1109
Downstream MH
02 1407
Dir. of Survey
Downstream
Length Surveyed
113.5 ft.
Total Length
113.5 ft.
Structural Index
3
Structural Quick
3C00
Structural Rating
63
O&M Index
2
O&M Quick
2F00
O&M Rating
72
Overall Index
2
Overall Quick
Overall Rating
135
Pipe schematic from manhole 02 1109 to 02 1407
MH: 02 1109MH: 02 1407downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 11098.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start23.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start23.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start113.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1407113.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 12 O'CLOCK113.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish113.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK113.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish113.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish

Observations (13)

DistanceCodeObservation
0MWL
113.5AMH02 1407
23.1DAGS
8.7CM
0MWM
113.5MGOACTIVE CONNECTION AT MH 12 O'CLOCK
113.5DAGS
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
23.1DAE
113.5MGOACTIVE CONNECTION AT MH 3 O'CLOCK
113.5CM
113.5DAE
0AMH02 1109

Properties (6)

additional_info
SC203945
custom_field_two
4
customer
LACSD
datetime
2015-10-26T06:57:04-07:00
documentation
PRO PIPE
is_lateral_inspection
false