Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 16, 2018, 10:28 AM
  • 15 0751_15 0750_4162018_052129.mp4

Date
04/16/2018
W/O
#
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12951
Time
3:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0823R
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Maintenance Related
Project
20180416MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0751
Downstream MH
15 0750
Dir. of Survey
Downstream
Length Surveyed
312 ft.
Total Length
312 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 0751 to 15 0750
MH: 15 0751MH: 15 0750downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 6 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 5:25AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active-OUTGOING LINE34.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open112.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open145.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open187.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS187.6 ft. RML - Roots Medium Lateral, from 07 to 10 o'clock, 20 %, within 8 inches of joint: YES206.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open269.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped272.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active303.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open312 ft. AMH - Downstream Manhole, Survey Ends - 5:45AM

Observation photos (2)

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS

    187.6 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS

  • Roots Medium Lateral, from 07 to 10 o'clock, 20 %, within 8 inches of joint: YES

    187.6 ft. - Roots Medium Lateral, from 07 to 10 o'clock, 20 %, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
0MWM
312AMH5:45AM
0MGOConn. @ Mh, 6 O' Clock. Active
0AMH5:25AM
0MWL
272.9TFActive
269.6TFCCapped
145.8TFOpen
303.2TFOpen
187.6TFDOpen-90% ROOTS
34.1TFOpen
112.5TFOpen
206.3TFOpen
0MGOConn. @ Mh, 3 O' Clock. Active-OUTGOING LINE
187.6RML

Properties (5)

additional_info
POST ROOT EVALUATION ONLY
customer
LACSD
datetime
2018-04-16T03:28:23-07:00
documentation
MARTIN,MANANES,OLIVER 111
is_lateral_inspection
false