Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 12, 2016, 07:53 PM
  • 22 0616_22 0615A_20160512_141856.mp4

Date
05/12/2016
W/O
568953
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00827
PipeID
P16964
Time
12:53 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3250
Sewer Name
22 SUNFLOWER TRUNK
City
GLENDORA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
21
Purpose
Routine Assessment
Project
WO_568953_TV22063_MAY2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0616
Downstream MH
22 0615A
Dir. of Survey
Downstream
Length Surveyed
285.3 ft.
Total Length
285.3 ft.
Structural Index
3
Structural Quick
3H00
Structural Rating
138
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
138
Pipe schematic from manhole 22 0616 to 22 0615A
MH: 22 0616MH: 22 0615Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 06160 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0.1 ft. MGO - General Observation - Magnesium hydroxide coating 75% start51.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"52.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - WANDERING110.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"122.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"142.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"186.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"192.7 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"208.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"212.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"282.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish285.3 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK285.3 ft. AMH - Downstream Manhole, Survey Ends - 22 0615A

Observation photos (4)

  • Water Mark, 20 %of cross sectional area

    0 ft. - Water Mark, 20 %of cross sectional area

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    51.7 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - WANDERING

    52.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - WANDERING

  • Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"

    192.7 ft. - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"

Observations (16)

DistanceCodeObservation
0AMH22 0616
186.7TFC
212.5TFC
285.3MGOCONNECTION AT THE MH 3 O'CLOCK
52.5SAVWANDERING
51.7TFC
142.8TFC
208.8TFC
0.1MGOMagnesium hydroxide coating 75% start
0MWL
0MWM
285.3AMH22 0615A
110.5TFC
282.1SAV
122.3TFA
192.7TBA

Properties (6)

additional_info
SC305349
custom_field_two
3
customer
LACSD
datetime
2016-05-12T12:53:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false