Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 16, 2016, 02:10 PM
  • 22 0615_22 0614_20160516_235609.mp4

Date
05/16/2016
W/O
568953
Weather
Dry
Operator/Surveyor
J. VARGAS
Sewer ID
Z00827
PipeID
P16962
Time
7:10 AM
Certificate
U-209-8149
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3457
Sewer Name
22 SUNFLOWER TRUNK
City
COVINA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
27
Purpose
Routine Assessment
Project
WO_568953_TV22063_MAY2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0615
Downstream MH
22 0614
Dir. of Survey
Downstream
Length Surveyed
437 ft.
Total Length
437 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
258
O&M Index
2
O&M Quick
2P12
O&M Rating
174
Overall Index
2
Overall Quick
Overall Rating
432
Pipe schematic from manhole 22 0615 to 22 0614
MH: 22 0615MH: 22 0614downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 06150 ft. MWL - Water Level, 35 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. MGO - General Observation - MAG COATING2 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start13 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"33.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"53.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"53.3 ft. VC - Vermin Cockroach, within 8 inches of joint: YES66.6 ft. VC - Vermin Cockroach, within 8 inches of joint: YES92.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"104.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"148.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"156.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"196.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4"212.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"232.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"245.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"276.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"307.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"363.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"364.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"404 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"423.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"433.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish433.9 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish437 ft. AMH - Downstream Manhole, Survey Ends - 22 0614

Observation photos (5)

  • General Observation - MAG COATING

    2 ft. - General Observation - MAG COATING

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Vermin Cockroach, within 8 inches of joint: YES

    53.3 ft. - Vermin Cockroach, within 8 inches of joint: YES

  • Vermin Cockroach, within 8 inches of joint: YES

    66.6 ft. - Vermin Cockroach, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
404TF
0AMH22 0615
232.5TFC
104.7TF
156.6TF
196.8TF
433.9DAGS
148.8TFA
92.7TF
212.4TF
433.9SAV
245.5TFA
53.3TF
2MGOMAG COATING
2SAV
53.3VC
437AMH22 0614
0MWL
33.4TF
307.8TF
2DAGS
364.6TFA
363.8TFC
13TF
423.6TF
0MWM
276.4TFC
66.6VC

Properties (6)

additional_info
SC305479
custom_field_two
3
customer
LACSD
datetime
2016-05-16T07:10:25-07:00
documentation
PROPIPE
is_lateral_inspection
false