Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 12, 2016, 05:58 AM
  • 22 0638_22 0637_20160512_001357.mp4

Date
05/11/2016
W/O
568953
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00827
PipeID
P16986
Time
10:58 PM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3249
Sewer Name
22 SUNFLOWER TRUNK
City
SAN DIMAS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
WO_568953_TV22063_MAY2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0638
Downstream MH
22 0637
Dir. of Survey
Downstream
Length Surveyed
208.4 ft.
Total Length
208.4 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
123
O&M Index
2
O&M Quick
2G11
O&M Rating
81
Overall Index
2
Overall Quick
Overall Rating
204
Pipe schematic from manhole 22 0638 to 22 0637
MH: 22 0638MH: 22 0637downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 06382 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - Magnesium hydroxide coating 85% start7.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start21.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"50.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4", 4"74.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"98 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"118.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"147 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"170.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"195.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4", 4"204.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish205 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish208.4 ft. AMH - Downstream Manhole, Survey Ends - 22 0637208.4 ft. VC - Vermin Cockroach

Observation photos (8)

  • Water Level, 15 %of cross sectional area

    0 ft. - Water Level, 15 %of cross sectional area

  • General Observation - CONNECTION AT THE MH 3 O'CLOCK

    0 ft. - General Observation - CONNECTION AT THE MH 3 O'CLOCK

  • General Observation - Magnesium hydroxide coating 85% start

    2 ft. - General Observation - Magnesium hydroxide coating 85% start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    21.5 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4", 4"

    50.3 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4", 4"

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4", 4"

    195.2 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4", 4"

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    204.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (19)

DistanceCodeObservation
170.9TFC
21.5TFC
0MWL
208.4AMH22 0637
74.1TFC
118.4TFC
98TFA
205SAV
0MGOCONNECTION AT THE MH 3 O'CLOCK
2SAV
7.1DAGS
208.4VC
195.2TFA
204.9DAGS
0MWM
0AMH22 0638
2MGOMagnesium hydroxide coating 85% start
147TFC
50.3TFA

Properties (6)

additional_info
SC305348
custom_field_two
3
customer
LACSD
datetime
2016-05-11T22:58:18-07:00
documentation
PRO PIPE