Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 6, 2016, 07:51 AM
  • 22 0685A_22 0685_20160506_020852.mp4

Date
05/06/2016
W/O
568953
Weather
Light Rain
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00827
PipeID
P17038
Time
12:51 AM
Certificate
U- 109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K 3203
Sewer Name
22 SUNFLOWER TRUNK
City
SAN DIMAS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
15
Purpose
Routine Assessment
Project
WO_568953_TV22063_MAY2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
22 0685A
Downstream MH
22 0685
Dir. of Survey
Downstream
Length Surveyed
346.6 ft.
Total Length
346.6 ft.
Structural Index
3
Structural Quick
3K00
Structural Rating
174
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
176
Pipe schematic from manhole 22 0685A to 22 0685
MH: 22 0685AMH: 22 0685downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK0 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 22 0685A2 ft. MGO - General Observation - Magnesium hydroxide coating 20% start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start57.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"63.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"75.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"132.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"137.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"207.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"212.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"281.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"286.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"343.6 ft. MGO - General Observation - Magnesium hydroxide coating 20% finish343.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish346.6 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK346.6 ft. MGO - General Observation - CONNECTION AT THE MH O'CLOCK346.6 ft. AMH - Downstream Manhole, Survey Ends - 22 0685346.6 ft. VC - Vermin Cockroach

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
346.6MGOCONNECTION AT THE MH 9 O'CLOCK
281.4TF
286.5TF
346.6MGOCONNECTION AT THE MH O'CLOCK
2MGOMagnesium hydroxide coating 20% start
212.1TF
207.1TFA
57.9TFC
75.1TB
63.2TFC
132.8TFC
343.6MGOMagnesium hydroxide coating 20% finish
0MGOCONNECTION AT THE MH 3 O'CLOCK
343.6SAV
346.6AMH22 0685
0VC
2SAV
346.6VC
0MWL
0MWM
137.5TF
0AMH22 0685A

Properties (6)

additional_info
SC300651
custom_field_two
3
customer
LACSD
datetime
2016-05-06T00:51:32-07:00
documentation
PRO PIPE
is_lateral_inspection
false