Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 10, 2016, 07:30 AM
  • 22 0663A_22 0663_20160509_014700.mp4

Date
05/10/2016
W/O
568953
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00827
PipeID
P17012
Time
12:30 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3247
Sewer Name
22 SUNFLOWER TRUNK
City
SAN DIMAS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
22
Purpose
Routine Assessment
Project
WO_568953_TV22063_MAY2016
Sewer Type
GRAVITY
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0663A
Downstream MH
22 0663
Dir. of Survey
Downstream
Length Surveyed
366.1 ft.
Total Length
366.1 ft.
Structural Index
3
Structural Quick
3M00
Structural Rating
216
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
220
Pipe schematic from manhole 22 0663A to 22 0663
MH: 22 0663AMH: 22 0663downstream0 ft. AMH - Upstream Manhole, Survey Begins - 22 0663A0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0.2 ft. MGO - General Observation - CONNECTION AT THE 9 MH O'CLOCK2 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - Magnesium hydroxide coating start3.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start57.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"62.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"121.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"126.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"141.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"176.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"216.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"251.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"280.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"315.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"320.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"362.6 ft. MGP - General Photograph - Magnesium hydroxide coating finish363.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish364 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish366.1 ft. AMH - Downstream Manhole, Survey Ends - 22 0663

Observation photos (2)

  • General Observation - Magnesium hydroxide coating start

    2 ft. - General Observation - Magnesium hydroxide coating start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
280.8TFA
362.6MGPMagnesium hydroxide coating finish
251.3TFA
2SAV
320.6TFA
315.7TFC
2MGOMagnesium hydroxide coating start
366.1AMH22 0663
0.2MGOCONNECTION AT THE 9 MH O'CLOCK
216.9TBA
363.4DAGS
0AMH22 0663A
62.4TFA
141.1TFA
3.4DAGS
176.4TFC
121.7TFA
0MWM
57.1TFA
126.7TFA
364SAV
0MWL

Properties (6)

additional_info
SC305346
custom_field_two
3
customer
LACSD
datetime
2016-05-10T00:30:06-07:00
documentation
PRO PIPE
is_lateral_inspection
false