Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 6, 2016, 08:54 AM
  • H 0550_H 0549_06052016_015515.mp4

Date
05/06/2016
W/O
568719
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00185
PipeID
P10974
Time
1:54 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3342
Sewer Name
H JOINT OUTFALL H - UNIT 8B
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
WO_568719_TV15169_MAY2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
H 0550
Downstream MH
H 0549
Dir. of Survey
Downstream
Length Surveyed
297.8 ft.
Total Length
297.8 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
295
O&M Index
2
O&M Quick
412K
O&M Rating
122
Overall Index
2
Overall Quick
Overall Rating
417
Pipe schematic from manhole H 0550 to H 0549
MH: H 0550MH: H 0549downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 05500 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start38.6 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"155.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"203.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"211 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"235.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"295.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish295.5 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish295.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish297 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK.297.5 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK.297.8 ft. AMH - Downstream Manhole, Survey Ends - H 0549297.8 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0.6 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    297.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
211TFC
295.4SSS
297MGOACTIVE CONNECTION AT MH 3 O'CLOCK.
0.6MGOCOCKROACHES IN MANHOLE
38.6TBA
297.5MGOACTIVE CONNECTION AT MH 9 O'CLOCK.
155.5TF
297.8AMHH 0549
2SSS
295.5SAV
235.2TFC
0AMHH 0550
295.5DAGS
0MWM
203.8TFA
227.5TFC
0MWL
2SAV
2DAGS
297.8MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC305619
custom_field_two
3
customer
LACSD
datetime
2016-05-06T01:54:54-07:00
documentation
PRO PIPE
is_lateral_inspection
false