Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 6, 2016, 08:28 AM
  • H 0551_H 0550_06052016_012920.mp4

Date
05/06/2016
W/O
568719
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00185
PipeID
P10975
Time
1:28 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3342
Sewer Name
H JOINT OUTFALL H - UNIT 8B
City
BALDWIN PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
WO_568719_TV15169_MAY2016
Sewer Type
GRAVITY
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Upstream MH
H 0551
Downstream MH
H 0550
Dir. of Survey
Downstream
Length Surveyed
590.5 ft.
Total Length
590.5 ft.
Structural Index
3
Structural Quick
3V2V
Structural Rating
585
O&M Index
2
O&M Quick
412V
O&M Rating
238
Overall Index
2
Overall Quick
Overall Rating
823
Pipe schematic from manhole H 0551 to H 0550
MH: H 0551MH: H 0550downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 05512 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start587.7 ft. MGO - General Observation - COCKROACHES IN MANHOLE587.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish587.7 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish587.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish590.5 ft. AMH - Downstream Manhole, Survey Ends - H 0550

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    587.7 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
2SAV
0MGOCOCKROACHES IN MANHOLE
2DAGS
590.5AMHH 0550
0MWM
2SSS
587.7MGOCOCKROACHES IN MANHOLE
0MWL
587.7SSS
587.7SAV
0AMHH 0551
587.7DAGS

Properties (6)

additional_info
SC305619
custom_field_two
3
customer
LACSD
datetime
2016-05-06T01:28:50-07:00
documentation
PRO PIPE
is_lateral_inspection
false