- Date
- 07/25/2017
- W/O
- 0651133
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00315
- PipeID
- P07767
- Time
- 1:22 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H0602
- Sewer Name
- A JOA-1A DISTRICT 5 INTERCEPTOR
- City
- GARDENA
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 20
- Purpose
- Routine Assessment
- Project
- 20170724MDM_JOA_1A_DISTRICT_5_INTERCEPTOR
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 54 in.
- Upstream MH
- A 0530
- Downstream MH
- A 0531
- Dir. of Survey
- Upstream
- Length Surveyed
- 6 ft.
- Total Length
- 6 ft.
- Structural Index
- 3
- Structural Quick
- 3121
- Structural Rating
- 5
- O&M Index
- 5
- O&M Quick
- 5100
- O&M Rating
- 5
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 10
Pipe schematic from manhole A 0530 to A 0531 Observation photos (4)

2 ft. - Lining Failure Detached, from 09 to 03 o'clock, within 8 inches of joint: NO - 60% EPOXY COATING REMAINING

3 ft. - General Observation - PEELING EPOXY COATING

4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - BLISTERING CONCRETE

6 ft. - Survey Abandoned - UPLEG DOWNSTREAM SIPHON