Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 29, 2017, 07:51 AM
  • 16 0544_16 0543 _29092017_005138.mp4

Date
09/29/2017
W/O
663060
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00659
PipeID
P13595
Time
12:51 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4281
Sewer Name
16 LAMANDA PARK TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
15
Purpose
Routine Assessment
Project
WO_663060_TV16078_OCT2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
16 0543
Downstream MH
16 0544
Dir. of Survey
Upstream
Length Surveyed
190.6 ft.
Total Length
190.6 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2F11
O&M Rating
75
Overall Index
2
Overall Quick
Overall Rating
81
Pipe schematic from manhole 16 0543 to 16 0544
MH: 16 0543MH: 16 0544upstream0 ft. AMH - Upstream Manhole, Survey Ends - 16 05440 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE0 ft. VC - Vermin Cockroach2.4 ft. MGO - General Observation - MAG COAT FINISH2.4 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"12 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"46.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"51.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"100 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"105.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"157.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"188.5 ft. MGO - General Observation - MAG COAT START188.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start188.5 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start190.6 ft. MWL - Water Level, 10 %of cross sectional area190.6 ft. MGO - General Observation - ACTIVE CONN. INSIDE THE MH. @ 06 O'CLOCK190.6 ft. MWM - Water Mark, 15 %of cross sectional area190.6 ft. AMH - Downstream Manhole, Survey Begins - 16 0543

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
178.6TFC
2.1MGOMAG COAT START
188.2MGOMAG COAT FINISH
190.6AMH16 0544
0MWL
184.6TFC
90.6TFC
0MGOACTIVE CONN. INSIDE THE MH. @ 06 O'CLOCK
190.6MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
2.1DAGS
188.2SAV
2.1SAV
138.8TFC
188.2DAGS
85.2TFC
0MWM
0AMH16 0543
144.1TFC
33.5TBA
190.6VC

Properties (6)

additional_info
SC352127
custom_field_two
3
customer
LACSD
datetime
2017-09-29T00:51:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false