Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 27, 2017, 06:16 AM
  • 08 0310_08 0309_26092017_231654.mpg

Date
09/26/2017
W/O
657837
Weather
Dry
Operator/Surveyor
CORTEZ ESTEBAN
Sewer ID
Z00013
PipeID
P00357
Time
11:16 PM
Certificate
U-209-8148
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4941
Sewer Name
08 KEYSTONE TRUNK
City
CARSON
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Routine Assessment
Project
WO_657837_TV08155_SEP2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
08 0310
Downstream MH
08 0309
Dir. of Survey
Downstream
Length Surveyed
347 ft.
Total Length
347 ft.
Structural Index
2
Structural Quick
2T00
Structural Rating
214
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
214
Pipe schematic from manhole 08 0310 to 08 0309
MH: 08 0310MH: 08 0309downstream0 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O' CLOCK AT MH0 ft. MGO - General Observation - SERVICE CONNECTION AT 9 O'CLOCK AT MH0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 031017.3 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start17.4 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start35.5 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish35.5 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish37.9 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"72.5 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"87.6 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start90.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start120.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"177.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"224.8 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"270 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4"319.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"343.1 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Finish343.1 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish346.9 ft. MGO - General Observation - CAPPED CONNECTION AT 3 O' CLOCK AT MH347 ft. AMH - Downstream Manhole, Survey Ends - 08 0309

Observation photos (4)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start

    17.3 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start

    17.4 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start

    87.6 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start

    90.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
72.5TFA
224.8TFA
0MGOCAPPED CONNECTION AT 3 O' CLOCK AT MH
17.4CL
0MGOSERVICE CONNECTION AT 9 O'CLOCK AT MH
87.6CL
35.5CL
0MWM
90.7CL
347AMH08 0309
35.5CL
177.5TFC
17.3CL
319.5TFC
0MWL
343.1CL
270TF
37.9TFC
346.9MGOCAPPED CONNECTION AT 3 O' CLOCK AT MH
0AMH08 0310
120.8TFC
343.1CL

Properties (6)

additional_info
SC345848
custom_field_two
2
customer
LACSD
datetime
2017-09-26T23:16:41-07:00
documentation
PRO-PIPE
is_lateral_inspection
false