Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 23, 2016, 08:18 AM
  • 02 0584_02 0583 _09232016_011828.mp4

Date
09/23/2016
W/O
592159
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00258
PipeID
P03128
Time
1:18 AM
Certificate
U-507-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3716
Sewer Name
02 EAST COMPTON BOULEVARD EXTENSION TRUNK
City
BELLFLOWER, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
WO_592159_TV02289_SEP2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 0584
Downstream MH
02 0583
Dir. of Survey
Downstream
Length Surveyed
326.9 ft.
Total Length
326.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
133
Pipe schematic from manhole 02 0584 to 02 0583
MH: 02 0584MH: 02 0583downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 05840 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start34.9 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 4"104 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"161.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"264.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 4"312.2 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES324.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish326.9 ft. AMH - Downstream Manhole, Survey Ends - 02 0583

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    312.2 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0AMH02 0584
326.9AMH02 0583
2DAGS
0MWM
324.6DAGS
161.2TFA
312.2CM
0MWL
264.9TFA
34.9TF
104TFA

Properties (6)

additional_info
SC303702
custom_field_two
4
customer
LACSD
datetime
2016-09-23T01:18:41-07:00
documentation
PRO-PIPE
is_lateral_inspection